Cable voltage drop
Calculate the voltage drop of a copper or aluminium cable, single- or three-phase, in volts and percent. Formula and steps. Simplified resistive formula: ΔV = k·ρ·L·I·cos φ / S, with k = 2 for single-phase/DC and k = √3 for three-phase. The calculator is free and shows the formula, the working and a numerical example, with no sign-up.
Results
⚠️ Indicative electrical calculation, NOT a design: cable section, ampacity and voltage drop must be verified by a qualified technician under IEC/EN, NEC and local regulations before any installation. Legal notice
Step-by-step calculation with your values
Formulas
\Delta V = \frac{k \cdot \rho \cdot L \cdot I \cdot \cos\varphi}{S}\Delta V\% = \frac{\Delta V}{V} \cdot 100How it is calculated
Simplified resistive formula: ΔV = k·ρ·L·I·cos φ / S, with k = 2 for single-phase/DC and k = √3 for three-phase. ρ is at 20 °C: at operating temperature (70–90 °C) resistivity rises about 20–25 %, and large cables add reactance.
Results are indicative: for real projects and installations always check applicable standards and a qualified professional.
Example
With the values: System = DC / single-phase; Conductor material = Copper; Cable length (one way) = 50 m; Current = 16 A; Conductor cross-section = 2.5 mm²; Power factor cos φ = 0.9; Voltage = 230 V — you get:
- Voltage drop: 10.253 V
- Voltage drop %: 4.4577 %
Frequently asked questions
Which formula does the “Cable voltage drop” calculator use?
Simplified resistive formula: ΔV = k·ρ·L·I·cos φ / S, with k = 2 for single-phase/DC and k = √3 for three-phase. ρ is at 20 °C: at operating temperature (70–90 °C) resistivity rises about 20–25 %, and large cables add reactance.
Is FunConvert free?
Yes. Every converter and calculator is free, with no sign-up and nothing to install. Calculations run in your browser.