Cable cross-section (size)
Calculate the minimum cable cross-section in mm² from the allowed voltage drop and get the next standard size. Single and three-phase. Inverting the voltage drop formula: S = k·ρ·L·I·cos φ / ΔVmax, with ΔVmax = ΔV% · V / 100. The calculator is free and shows the formula, the working and a numerical example, with no sign-up.
Results
⚠️ Indicative electrical calculation, NOT a design: cable section, ampacity and voltage drop must be verified by a qualified technician under IEC/EN, NEC and local regulations before any installation. Legal notice
Step-by-step calculation with your values
Formulas
\Delta V_{max} = \frac{\Delta V\% \cdot V}{100}S_{min} = \frac{k \cdot \rho \cdot L \cdot I \cdot \cos\varphi}{\Delta V_{max}}S_{std} = \lceil S_{min} \rceil_{std}How it is calculated
Inverting the voltage drop formula: S = k·ρ·L·I·cos φ / ΔVmax, with ΔVmax = ΔV% · V / 100. Round up to the next standard size and also check current-carrying capacity (IEC 60364) and protection.
Results are indicative: for real projects and installations always check applicable standards and a qualified professional.
Example
With the values: System = DC / single-phase; Conductor material = Copper; Cable length (one way) = 50 m; Current = 16 A; Power factor cos φ = 0.9; Voltage = 230 V; Allowed voltage drop = 4 % — you get:
- Allowed voltage drop: 9.2 V
- Minimum cross-section: 2.7861 mm²
- Suggested standard size: 4 mm²
Frequently asked questions
Which formula does the “Cable cross-section (size)” calculator use?
Inverting the voltage drop formula: S = k·ρ·L·I·cos φ / ΔVmax, with ΔVmax = ΔV% · V / 100. Round up to the next standard size and also check current-carrying capacity (IEC 60364) and protection.
Is FunConvert free?
Yes. Every converter and calculator is free, with no sign-up and nothing to install. Calculations run in your browser.