Thermal power from flow and ΔT
Calculate the thermal power of a water circuit (heating, cooling) from flow rate, temperature difference and specific heat. Power = mass flow × specific heat × temperature difference: P = ṁ·cp·ΔT, with ṁ = Q·ρ. The calculator is free and shows the formula, the working and a numerical example, with no sign-up.
Results
Indicative results: always verify with a qualified technician and the applicable standards. Legal notice
Step-by-step calculation with your values
Formulas
\dot m = \frac{Q \cdot \rho}{3600}P = \dot m \cdot c_p \cdot \Delta THow it is calculated
Power = mass flow × specific heat × temperature difference: P = ṁ·cp·ΔT, with ṁ = Q·ρ. For water the rule of thumb is P[kW] ≈ 1.163·Q[m³/h]·ΔT.
Results are indicative: for real projects and installations always check applicable standards and a qualified professional.
Example
With the values: Flow rate = 2 m³/h; Temperature difference ΔT = 10 K; Fluid density = 1,000 kg/m³; Specific heat cp = 4.186 kJ/(kg·K) — you get:
- Mass flow rate: 0.55556 kg/s
- Thermal power: 23.256 kW
Frequently asked questions
Which formula does the “Thermal power from flow and ΔT” calculator use?
Power = mass flow × specific heat × temperature difference: P = ṁ·cp·ΔT, with ṁ = Q·ρ. For water the rule of thumb is P[kW] ≈ 1.163·Q[m³/h]·ΔT.
Is FunConvert free?
Yes. Every converter and calculator is free, with no sign-up and nothing to install. Calculations run in your browser.