🎒 SchoolNEW 💡 Suggest

Thermal power from flow and ΔT

Calculate the thermal power of a water circuit (heating, cooling) from flow rate, temperature difference and specific heat. Power = mass flow × specific heat × temperature difference: P = ṁ·cp·ΔT, with ṁ = Q·ρ. The calculator is free and shows the formula, the working and a numerical example, with no sign-up.

Results

Indicative results: always verify with a qualified technician and the applicable standards. Legal notice

Step-by-step calculation with your values

    Formulas

    \dot m = \frac{Q \cdot \rho}{3600}
    P = \dot m \cdot c_p \cdot \Delta T

    How it is calculated

    Power = mass flow × specific heat × temperature difference: P = ṁ·cp·ΔT, with ṁ = Q·ρ. For water the rule of thumb is P[kW] ≈ 1.163·Q[m³/h]·ΔT.

    Results are indicative: for real projects and installations always check applicable standards and a qualified professional.

    Example

    With the values: Flow rate = 2 m³/h; Temperature difference ΔT = 10 K; Fluid density = 1,000 kg/m³; Specific heat cp = 4.186 kJ/(kg·K) — you get:

    • Mass flow rate: 0.55556 kg/s
    • Thermal power: 23.256 kW

    Frequently asked questions

    Which formula does the “Thermal power from flow and ΔT” calculator use?

    Power = mass flow × specific heat × temperature difference: P = ṁ·cp·ΔT, with ṁ = Q·ρ. For water the rule of thumb is P[kW] ≈ 1.163·Q[m³/h]·ΔT.

    Is FunConvert free?

    Yes. Every converter and calculator is free, with no sign-up and nothing to install. Calculations run in your browser.

    What do you think?